EXPERIMENTAL INVESTIGATION OF TRANSCRITICAL CO2 HEAT PUMP FOR SIMULTANEOUS WATER COOLING AND HEATING
Abstract
This paper presents the experimental performances of a transcritical CO2 heat pump prototype for simultaneous water cooling and heating applications. System behavior and performances such as cooling capacity, heating capacity, and system coefficient of performance (COP) have been studied experimentally for various operating parameters such as water mass flow rate, water inlet temperature for both evaporator and gas cooler, and expansion valve opening. Performance is also compared with previous test data. Test indicates that the expansion valve opening has a significant effect as well near the full valve closing condition (up to 20°). Study shows that both the water mass flow rate and inlet temperature have significant effect on system performances. Test results show that, at gas cooler pressure of 90 bar, the effect of evaporator water mass flow rate on the system performances is more pronounced (COP increases 0.6 for 1 kg/min.) compared to the gas cooler water mass flow rate (COP increases 0.4 for 1 kg/min.) and the effect of gas cooler water inlet temperature is more significant (COP decreases 0.48 for given ranges) compared to the evaporator water inlet temperature (COP increases 0.43 for given ranges).
Dates
- Submission Date2008-08-22
- Revision Date2009-07-13
- Acceptance Date2009-08-03
References
- Neksa, P., CO2 Heat Pump Systems, International Journal of Refrigeration, 25 (2002), 4, pp. 421-427
- Kim, M. H., Pettersen, J., Bullard, C. W., Fundamental Process and System Design Issues in CO2 Vapor Compression Systems, Progress in Energy and Combustion Science, 30 (2004), 2, pp. 119-174
- Neksa, P., Rekstad, H., Zakeri, G. R., Schiefloe, P. A., CO2 Heat Pump Water Heater: Characteristics, System Design & Experimental Results, International Journal Refrigeration, 21 (1998), 3, pp. 172-179
- White, S. D., Yarrall, M. G., Cleland, D. J., Hedley, R. A., Modelling the Performance of a Transcritical CO2 Heat Pump for High Temperature Heating, International Journal of Refrigeration, 25 (2002), 4, pp. 479-486
- Hwang, Y., Radermacher, R., Experimental Investigation of the CO2 Refrigeration Cycle, ASHRAE Transactions, 105 (1999), 1, pp. 1219-1228
- Yarral, M. G., et. al., Performance of Transcritical CO2 Heat Pump for Simultaneous Refrigeration and Water Heating, Proceedings, XX International Congress of Refrigeration, Sydney, 1999, Paper 651
- Adriansyah, W., Combined air Conditioning and Tap Water Heating Plant Using CO2 as Refrigerant, Energy and Buildings, 36 (2004), 7, pp. 690-695
- Stene, J., Residential CO2 Heat Pump System for Combined Space Heating and Hot Water Heating, International Journal of Refrigeration, 28 (2005), 8, pp. 1259-1265
- Cho, H., Ryu, C., Kim, Y., Effects of Refrigerant Charge Amount on the Performance of a Transcritical CO2 Heat Pump, International Journal of Refrigeration, 28 (2005), 8, pp. 1266-1273
- Kim, S. G., et al.,The Performance of a Transcritical CO2 Cycle with an Internal Heat Exchanger for Hot Water Heating, International Journal of Refrigeration, 28 (2005), 7, pp. 1064-1072
- Cabello, R., et al., Experimental Evaluation of the Energy Efficiency of a CO2 Refrigerating Plant Working in Transcritical Conditions, Applied Thermal Engineering, 28 (2008), 13, pp. 1596-1604
- Sarkar, J., Bhattacharyya, S., Ramgopal, M., Optimization of a Transcritical CO2 Heat Pump Cycle for Simultaneous Cooling and Heating Applications, International Journal of Refrigeration, 27 (2004), 8, pp. 830-838
- Sarkar, J., Bhattacharyya, S., Ramgopal, M., Simulation of a Transcritical CO2 Heat Pump Cycle for Simultaneous Cooling and Heating Applications, International Journal of Refrigeration, 29 (2006), 5, pp. 735-743
- Sarkar, J., Bhattacharyya, S., Ramgopal, M., Transcritical CO2 Heat Pump Prototype Development for Simultaneous Water Cooling and Heating, Proceedings, 22nd International Congress of Refrigeration, Beijing, 2007, Paper-548
Volume
14,
Issue
1,
Pages57 -64